modbus, modbus rtu, modbus tcp, modbus protocol, modbus linux, modbus source
code, modbus specification, modbus ascii, modbus通訊協定,
what is modbus, Unigate CL gateway
Part No:MPGC-MB-GW-PKV3500-DH+
Description: The
PKV3500-DH+/Modbus provides high speed interconnectivity
between an Allen-Bradley DH+ and a Modbus network. The -DH+/Modbus can be
any station on DH+ and can be set to either Modbus Master or Modbus Slave.
Master mode enables any DH+ station to read / write up to 100 words (per
message) to any 4xxxx or 0xxxx register, and to read up to 100 words from
the 1xxxx and 3xxxx registers at any Modbus Slave address from 1 to 255.
Slave mode enables a Modbus Master to read or write up to 1600 coils or 100
registers (per message) to bit or integer files in any PLC-5 station on DH+
(except 0). Modbus commands to address 0 can be "broadcast" to a selected
range of DH+ stations. Modbus Plus Connectivity: Provides an interface to
Modbus Plus via a Modicon BM85 Modbus Plus Bridge/Multiplexer.
Serial Interfacing:
CHA - DH+
CHB - Serial 300 b to 230.4 Kb or USB Interface (Modbus)
Specifications:
Physical
Dimensions Size: 1.2〞H x 4.75〞D x 3.2〞W (30.4 mm x 120.7 mm x 81.3 mm),
Weight: 0.56lbs (0.194 kg) Power: DC: 9-27 VDC; Less than 2 Watts.
Installation
Metal enclosure; Freestanding, DIN rail mounting clips, or #8 bolts.
Environment
Operating: +32 F to 122 F (0 C to +50 C), Storage: -40 F to +185 F (-40
C to +85 C), Humidity: 5% to 95% non-condensing.
Indicators
Green LED for power-on Red/Green BI-Color LED’s for communications.
Pushbuttons
Reset and Configure/Diagnostics mode pushbuttons.
Communications
Channel A: DH+, Channel B: Serial 300 b to 230.4 Kb or USB.
Connectors
CHA: 3-pin DH+, CHB: 9-pin RS232, 5-pin RS422/RS485, and USB, Power:
3-pin Miniature Phoenix Euro.
|
|